The Alfen Linea consumer substation is delivered with the following specifications.
| Construction type | Prefab concrete with detachable roof |
|---|---|
| Dimensions | 245 x 134 x 202 cm (L x W x H) (height above surface level) |
| Clearance MV opening | 210 x 130 cm (W x H) |
| Clearance LV opening | 69 x 100 cm (W x H) |
| Lock | Door handle with 17 mm euro profile cylinder |
| Cable entries MV side | Access via detachable front cover panel |
| Cable entries LV side | Closed system with cable glands |
| MV installation dimensions (max) | 180 x 80 x 160 cm (W x D x H) |
| LV installation dimensions (max) | 70 x 100 x 30 cm |
| Weight casing | 4,350 kg |
| Design standard | IEC 62271-202 |
| Temperature class | N/A |
| Finishing concrete | Exposed concrete light grey, anti-graffiti coating. |
| Finishing cover panels | Color light grey (RAL 7044) |
| Lighting MV and LV area | Lamp operated by door switch |
| Wall socket MV and LV area | Wall socket with 16A grounding |
| Security lighting | 16A circuit breaker |
| RCCB | 25A 30mA |
| Power supply | 230V-50hZ |
| Grounding equipment | Equipment and metal parts connect to grounding bus bar |
| Grounding electrode MV area | Aansluitklem 25-95mm2 |
| Connection point grounding equipment MV area | Ball knob round 25mm |